Louver Valve
video

Louver Valve

The Louver Valve is used in air ducts and flue gas pipelines to regulate the flow area by rotating multiple parallel blades. The blade angle controls the air or flue gas flow through the duct. When the blades are aligned with the airflow, the passage is fully open. When the blades rotate to the closed position, the flow passage is shut off.
Send Inquiry
Product Introduction

Control Air Flow with Blades

 

The Louver Valve is used in air ducts and flue gas pipelines to regulate the flow area by rotating multiple parallel blades. The blade angle controls the air or flue gas flow through the duct. When the blades are aligned with the airflow, the passage is fully open. When the blades rotate to the closed position, the flow passage is shut off. Round sizes range from DN200 to DN1600, while square sizes range from 300×300 to 1500×1500 mm. The number of blades varies with the opening size. Units up to DN300 use three blades, DN500–DN800 units use five to seven blades, and units of DN1000 and above use nine to thirteen blades. The drive uses a DYHQ hydraulic rotator with torque from 100 to 1000 N·m. The blade angle can be adjusted steplessly from 0 to 90 degrees. Control linearity is within ±3%, with a 4–20 mA input corresponding to 0–100% opening. The blade edges use fluoroelastomer sealing strips, with a leakage rate below 3%. The standard version is rated for temperatures up to 120°C, while the high-temperature version uses 304 stainless steel blades and is rated for up to 350°C.

product-800-800

Pressure Drop Tested in Our Duct

 

The Louver Valve is manufactured according to GB/T 10595-2017 and JB/T 12705-2016. The factory also tests the flow resistance of the valve in the fully open position. During the test, the valve is installed in a duct and air is driven through the system by a fan. Pressure is measured upstream and downstream of the valve to determine the pressure drop and flow resistance. A lower pressure drop indicates lower resistance to airflow and can help reduce the fan power required for the same operating conditions. In the factory comparison test, the fully open resistance factor was approximately 15% lower than that of a butterfly valve with the same nominal opening. The result is included in the product documentation for system design reference. Blade angle and blade profile are key factors affecting flow resistance. The factory has changed the blade profile from a flat plate to a slightly curved aerodynamic section to reduce resistance in the fully open position.

product-800-800

 

Specifications

 

Parameter

Content

Opening size

Round DN200 to DN1600 / Square 300×300 to 1500×1500 mm

Blade count

DN300 and below: 3 blades / DN500–DN800: 5–7 blades / DN1000 and above: 9–13 blades

Drive type

DYHQ hydraulic rotator, torque 100–1000 N·m

Setting angle

0–90 degrees, stepless adjustment

Control linearity

±3%; 4–20 mA corresponds to 0–100% opening

Seal material

Fluoroelastomer sealing strip at blade edges

Standard leakage rate

≤3%

Normal-temperature version

Up to 120°C

High-temperature version

Up to 350°C, with 304 stainless steel blades

Standards

GB/T 10595-2017, JB/T 12705-2016

Common applications

Duct airflow regulation, fine flow adjustment in powder conveying pipelines

 

FAQ

 

 

Q: How accurate is the opening setting?

A: The specified control linearity is within ±3%. A 50% input signal corresponds to a nominal 50% opening, with the stated control range allowing approximately 47–53% opening.

Q: Why is the pressure drop lower than a butterfly valve?

A: The blade profile was changed from a flat plate to a slightly curved aerodynamic section. In the factory comparison test, the fully open resistance factor was approximately 15% lower than that of a butterfly valve with the same nominal opening.

 

Hot Tags: louver valve, China louver valve manufacturers, suppliers, factory, 3 Way Gravity Diverter Valve, Ash Discharge Valve, Rake Gate, Sector Gate, Silo Slide Gate, slide gate